New residential AC and heat pump systems in the U.S. now ship with A2L refrigerants, mainly R-454B and R-32. R-410A isn't banned: existing systems can be serviced, and since a May 2026 rule, R-410A equipment made or imported before January 1, 2025 can still be installed until the inventory runs out. What changed for good is everything around a new install: the equipment listing, the code checklist, the tools, the cylinders and the price.
This guide explains what A2L means, how the refrigerants compare (including where sources disagree on GWP), the actual EPA timeline, a field checklist built from UL's code guidance, and how to price and talk about it with customers. Regulatory facts were checked against EPA, the Federal Register and the eCFR in October 2026. Where the rules are still moving, we say so.
30%
HFC production and consumption allowed in 2029 to 2033, as a share of baseline (60% today)
What "A2L" means
ASHRAE Standard 34 gives each refrigerant a safety group: a letter for toxicity (A lower, B higher) and a number for flammability (1 no flame propagation, 2L lower flammability, 2 flammable, 3 higher flammability). The "L" subclass is for refrigerants whose burning velocity is under 10 centimeters per second; ACHR News reported R-32 at 6.7 cm/s and R-454B at 5.2 cm/s1. In practice, A2Ls are hard to ignite and burn slowly, but a large enough leak meeting a strong enough ignition source in a confined space can burn. That's why A2L equipment, codes and tools carry safety requirements R-410A never needed.
EPA's SNAP listings for residential and light commercial AC show the classes side by side: R-410A is A1, R-32 and R-454B are A2L, and propane (R-290) is A3, acceptable only in self-contained room air conditioners2.
R-454B vs R-32 vs R-410A
| R-410A | R-454B | R-32 | R-454C | |
|---|---|---|---|---|
| Safety group | A1 | A2L | A2L | A2L |
| Composition (ASHRAE 34)3 | R-32/R-125 (50/50) | R-32/R-1234yf (68.9/31.1) | Single component | R-32/R-1234yf (21.5/78.5) |
| GWP by EPA's blend method4 | ~2,088 | ~465 | 675 | ~146 |
| GWP in EPA's SNAP table2 | 2,090 | 470 | 675 | 150 |
| New residential split systems (700 limit) | Only pre-2025 components | Yes | Yes | Yes |
Why the GWP numbers differ. EPA's AIM Act rules calculate a blend's GWP by weighting each component: R-32 at 675, R-125 at 3,500, R-1234yf at 14. That gives about 2,088 for R-410A and 465 for R-454B. EPA's own SNAP table rounds to 2,090 and 470, and refrigerant makers often publish 466 for R-454B. The difference doesn't matter for compliance (every A2L here is well under 700), but if a spec sheet and a regulation disagree, the regulation's method is the one that counts.
Blend GWP (40 CFR 84.64(b))
Which refrigerant you handle depends on the brand: manufacturers chose different refrigerants for their residential lines, so many shops now stock and service both. They are not interchangeable. Each system is designed, tested and certified for one refrigerant.
The EPA timeline: what's restricted and when
The restrictions come from the AIM Act's Technology Transitions program. The residential and light commercial rules have changed several times5:
October 2023
Original Technology Transitions rule
Restricts higher-GWP HFCs in new equipment across many sectors. Residential and light commercial AC and heat pumps: 700 GWP limit.
December 2023
Interim final rule
Systems using components made or imported before January 1, 2025 may be installed until January 1, 2026.
December 2024
VRF rule
New VRF above 700 GWP can be installed until January 1, 2027 if all components were made or imported before January 1, 2026; until January 1, 2028 with a building permit issued before October 5, 2023.
January 1, 2025
700 limit takes effect
Self-contained units (window, portable): manufacture and import. Split systems: installation, unless all specified components were made or imported before this date.
October 3, 2025
Reconsideration proposed
EPA proposes removing the January 1, 2026 installation deadline for pre-2025 equipment.
May 26, 2026
Reconsideration final
Removes the January 1, 2026 installation date for pre-2025 residential and light commercial systems, allowing that inventory to be installed until supply runs out. Also relaxes limits and timelines for supermarkets, remote condensing units and cold storage.
The May 2026 rule, signed May 21 and published May 26, says it allows pre-2025 inventory of AC systems to be installed until supply runs out67. EPA's sector table, updated August 28, 2026, now shows split systems with a January 1, 2025 installation date and a footnote: no installation date applies where all specified components were manufactured or imported before January 1, 20258.
R-410A for service, and why it will cost more
Technology Transitions doesn't restrict servicing existing systems. But R-410A is an HFC, and total HFC production and consumption is capped as a share of the historical baseline4:
Caps are in exchange-value-weighted tons, so high-GWP refrigerants like R-410A use up allowance fastest.
| 2022 to 2023 | 90% |
|---|---|
| 2024 to 2028 | 60% |
| 2029 to 2033 | 30% |
| 2034 to 2035 | 20% |
| 2036 onward | 15% |
Source: 40 CFR 84.7
The 2029 step halves the cap. Recovered and reclaimed R-410A will matter more, and from January 1, 2029 the AIM Act reclaim rule requires reclaimed refrigerant for servicing supermarket systems, refrigerated transport and automatic commercial ice makers (not residential AC)9. For a homeowner with an older R-410A system and a big leak, future refrigerant cost is a fair factor in a repair-or-replace conversation.
What changes on the install
The equipment listing and the code
A2L equipment is certified to UL 60335-2-40. EPA's SNAP use conditions for these refrigerants in residential AC currently reference the standard's 3rd edition; EPA proposed updating the use conditions in SNAP Proposed Rule 27 (November 2025), which EPA's page still shows as proposed, not final10. The 2024 International Residential Code, section M1411.2, requires A2L appliances to be certified to UL 60335-2-40 and installed per the manufacturer's instructions; the 2024 IMC and UMC have matching requirements1112.
UL Solutions publishes a free install checklist for each code. Here's the IRC 2024 version, condensed11:
A2L residential install checks (from UL's IRC 2024 checklist)
- Integral refrigerant detection system (RDS) installed if the manufacturer requires it, correct part number, sensors in the right spot for the air handler orientation (A2Ls are heavier than air, so sensors usually sit low, below the coil), wired per the diagram
- Ducted, no zoning: total room area served is above the minimum room size
- Ducted with zoning: smallest zone is above the minimum room size, or the zone system opens all zones when the RDS detects a leak
- Ductless: the room is above the minimum room size for the unit's mounting height
- Charge under 34.5 lb per independent system (IRC M1411.6)
- Field-installed heater kit is identified on the nameplate
- No electric heating elements, open flames or devices switching loads above 2.5 kVA in the ductwork; duct-mounted ignition sources interlocked with airflow or shut off when the RDS trips
- Safety shutoff valves installed if the manufacturer specifies them
- Piping installed, protected, pressure and leak tested per the manufacturer; press-connect fittings certified for A2L
- Refrigerant type and field-adjusted charge written on the unit label, with the installing company's contact information
- Installation instructions and service manuals left on site for the inspector
UL notes that RDS and minimum room size typically apply to equipment with more than about 2 pounds of charge for non-fixed factory-sealed units, or about 4 pounds for other equipment11. For commercial work, the IMC and UMC checklist adds design to ASHRAE 15, effective dispersal volume calculations, pipe labeling ("WARNING – Risk of Fire. Flammable Refrigerant") and a limit on hot surfaces above 1,290°F in ductwork unless interlocked with airflow12.
States and cities adopt code editions on their own schedules, often with amendments. Before your first A2L install in a jurisdiction, ask the building department which edition applies.
Tools
Anything that touches the refrigerant circuit, or could be an ignition source near a leak, should be rated for A2L: recovery machines, vacuum pumps (spark-free switching) and electronic leak detectors. Many manifolds and hoses work for both, but many shops keep separate A1 and A2L sets to avoid cross-contamination. Check the tool maker's listing, not just the box.
Cylinders
From ACCA's guidance13:
- Gray body, red band. Cylinders are now gray with the ASHRAE R-number. A2L cylinders must also carry a red band at the top, and the box carries a flammable placard.
- Left-hand threads. Most makers moved A2L cylinders to a left-hand thread (CGA 164) fitting. That's an AHRI guideline, not a legal requirement, so stock adapters.
- Relief valves, not rupture discs. A2L cylinders require resealable pressure relief valves. ACCA warns that non-compliant imported cylinders with rupture discs have shown up in the U.S. market. Buy from reputable suppliers.
- Storage. Relief valve in the vapor space, pointing up; never above 125°F, the maximum for any refrigerant cylinder.
- Smaller fills. Fill weights dropped from 30 to 20 pounds because shipping fill limits depend on refrigerant density.
- Heels. From January 1, 2028, used disposable cylinders must go to a reclaimer or a processor that removes the heel, or a certified tech evacuates the heel to 15 inches of mercury vacuum and signs a statement9.
Certification and training
EPA Section 608 already covers A2Ls: since January 1, 2018, certification applies to appliances containing any non-exempt substitute refrigerant14. As of October 2026 we found no separate federal A2L certification. Train every tech before they open their first A2L system anyway. Brazing, leak testing and charging follow each manufacturer's A2L procedures, and the code checklist above is new to most crews. See our EPA 608 guide for the rest of the refrigerant rules.
Pricing and customer conversations
The transition raised costs in several places at once: new equipment, refrigerant and cylinder supply (R-454B and especially 20-pound A2L cylinders were short at times in 2025, according to the ICC15), A2L-rated tools, training time, and longer installs while crews learn the RDS wiring, room-size checks and labeling. We don't publish "typical" increases because they vary by brand, region and distributor.
Instead, rebuild replacement prices from your actual costs:
A2L replacement price rebuild
Use actual hours from your last several A2L installs, not your R-410A install times. Our HVAC pricing guide covers the selling rate and margin math.
Free download · ExcelFlat-Rate Price Book BuilderWork out your true hourly cost, set your billable rate, and price every task with good, better and best options.Talking to customers. Short, calm, accurate answers build trust:
- "Do I have to replace my R-410A system?" No. Existing systems can be serviced and repaired. The rules apply to new equipment.
- "Is the new refrigerant safe?" A2Ls are classified lower toxicity and lower flammability. The equipment is certified to a safety standard written for them, often with a leak sensor, and installers follow specific code requirements.
- "Will repairs on my old system get more expensive?" Possibly, as R-410A supply shrinks with the HFC cap. It's one factor in a repair-or-replace decision, alongside age, efficiency and repair history.
- "Should I buy an R-410A system while I can?" Pre-2025 R-410A equipment can still be installed legally. It may cost less up front and can be serviced for its life, but future refrigerant may cost more. Show it next to an A2L option and let the customer choose.
A good-better-best estimate is the natural place for that last conversation, with the refrigerant noted on each option. In TradesWork, equipment records keep refrigerant type, age and service history for every unit, so techs know whether they're walking into an R-22, R-410A, R-454B or R-32 home before they arrive, and every charge and recovery is logged per unit and per tech with the tech's EPA 608 number.
A2L transition checklist for owners
- Every tech trained on A2L handling and the code install checklist.
- A2L-rated recovery machine, vacuum pump and leak detector on every truck that installs or services A2L systems.
- Left-hand thread adapters and A2L recovery cylinders stocked; no rupture-disc cylinders.
- UL's code checklist printed for each crew, and installation manuals reviewed for each model you sell.
- Code edition and amendments confirmed with each building department you work in.
- Replacement prices rebuilt from current equipment costs and actual A2L install hours.
- CSRs and techs given the four customer answers above.
- Refrigerant type recorded on every equipment record.
- EPA's sector table checked at least twice a year.
Footnotes
-
ACHR News, "A2L Terms You Should Know," June 4, 2022 (trade press). https://www.achrnews.com/articles/146639-a2l-terms-you-should-know ↩
-
U.S. EPA, SNAP, Substitutes in Residential and Light Commercial Air Conditioning and Heat Pumps (last updated March 19, 2026). https://www.epa.gov/snap/substitutes-residential-and-light-commercial-air-conditioning-and-heat-pumps ↩ ↩2
-
ASHRAE, Refrigerant Designations (Standard 34 compositions). https://www.ashrae.org/technical-resources/standards-and-guidelines/ashrae-refrigerant-designations ↩
-
40 CFR Part 84: 84.7 (phasedown schedule), 84.64(b) (blend GWP method and Table 1, HFO-1234yf = 1) and Appendix A (HFC-32 = 675, HFC-125 = 3,500). https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84 ↩ ↩2 ↩3
-
U.S. EPA, Regulatory Actions for Technology Transitions (last updated July 28, 2026). https://www.epa.gov/hfcs/regulatory-actions-technology-transitions ↩
-
U.S. EPA, Fact Sheet, Final Rule: Reconsideration of Certain Regulatory Requirements Promulgated under the Technology Transitions Provisions, May 2026. https://www.epa.gov/system/files/documents/2026-05/fact-sheet-san-12166-technology-transitions-frm.pdf ↩
-
Federal Register, Phasedown of Hydrofluorocarbons: Reconsideration of Certain Regulatory Requirements Promulgated Under the Technology Transitions Provisions, May 26, 2026. https://www.federalregister.gov/documents/2026/05/26/2026-10387/phasedown-of-hydrofluorocarbons-reconsideration-of-certain-regulatory-requirements-promulgated-under ↩
-
U.S. EPA, Technology Transitions HFC Restrictions by Sector (last updated August 28, 2026). https://www.epa.gov/climate-hfcs-reduction/technology-transitions-hfc-restrictions-sector ↩
-
40 CFR Part 84, Subpart C: 84.112 (reclamation, servicing with reclaimed HFCs from Jan 1, 2029) and 84.116 (disposable cylinders from Jan 1, 2028). https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-C ↩ ↩2
-
U.S. EPA, SNAP Regulations, Proposed Rules and Final Rules (Proposed Rule 27, November 2025; supplemental proposal April 2026). https://www.epa.gov/snap/regulations-proposed-rules-and-final-rules-determined-epa ↩
-
UL Solutions, A2L HVAC System Installation Checklist, International Residential Code (IRC-2024), Rev. 03/2025. https://www.ul.com/sites/default/files/2025-03/International_Residential_Code_IRC-2024.pdf ↩ ↩2 ↩3
-
UL Solutions, A2L HVAC System Installation Checklist, IMC-2024 and UMC-2024, Rev. 03/2025. https://www.ul.com/sites/default/files/2025-03/International_Mechanical_Code_IMC-2024_Uniform_Mechanical_Code_UMC-2024.pdf ↩ ↩2
-
ACCA HVAC Blog, "Where Did All the Colors Go? What Contractors Need to Know About the Switch to Gray A2L Cylinders," December 5, 2025 (sponsored post). https://hvac-blog.acca.org/where-did-all-the-colors-go-what-contractors-need-to-know-about-the-switch-to-gray-a2l-cylinders/ ↩
-
40 CFR 82.161, Technician certification. https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.161 ↩
-
International Code Council, Building Safety Journal, "Q4 2025 Update: EPA's Technology Transitions Program Related to A2L Refrigerants," November 13, 2025. https://www.iccsafe.org/building-safety-journal/bsj-technical/q4-2025-update-epas-technology-transitions-program-related-to-a2l-refrigerants/ ↩