Subcooling in HVAC: the formula, how to measure it on the liquid line, using the manufacturer's target on TXV systems, and what high and low readings mean.

Updated October 15, 2026 · 5 min read

Definition

Subcooling is how many degrees the liquid refrigerant in the liquid line is below its saturation (condensing) temperature at the measured pressure. You find it by subtracting the liquid line temperature from the condenser saturation temperature. It is the standard way to check the charge on systems with a TXV or electronic expansion valve.

Also called: liquid subcooling, SC

Formula

Subcooling = condenser saturation temperature − liquid line temperature

Example: 105°F saturation − 95°F line = 10°F subcooling

Measured as
Condenser saturation temp − liquid line temp (°F)
Where
Liquid line, near the outdoor unit's service valve
Charging method for
TXV and electronic expansion valve systems
Target from
Manufacturer, usually on the outdoor unit's nameplate or charging chart
ENERGY STAR tolerance
Within ±3°F of the manufacturer's target

Subcooling is the liquid-side twin of superheat. In the condenser, hot refrigerant vapor gives up heat and turns back into liquid. Once it's all liquid, it can keep cooling below its condensing temperature. That extra drop is the subcooling, and it tells you how much liquid is backed up in the condenser.

Subcooling in plain English

The condenser holds a mix: vapor coming in at the top, liquid draining out at the bottom. The more refrigerant in the system, the more of the condenser fills with liquid, and the longer that liquid sits in the outdoor air cooling off. So more charge usually means more subcooling.

DOE's Building America measure guideline defines it as the difference between the liquid line refrigerant temperature and the liquid saturation temperature at the measured pressure1. A healthy number means the metering device is getting a solid column of liquid, not a mix of liquid and flash gas.

How do you calculate subcooling?

  1. 1

    Run the system 15 minutes

    Let pressures settle before reading, as ENERGY STAR's checklist and DOE's guide both require.

  2. 2

    Read liquid line pressure

    Connect the high-side gauge to the liquid line service port.

  3. 3

    Convert to condensing saturation temperature

    Use the PT chart for the refrigerant on the nameplate. On a blend, use the liquid (bubble) side unless the manufacturer says otherwise.

  4. 4

    Clamp a thermometer on the liquid line

    Near the service valve, on clean pipe, insulated from the air.

  5. 5

    Subtract

    Saturation temperature minus liquid line temperature is the actual subcooling.

Formula

Subcooling (°F) = condenser saturation temperature − liquid line temperature

Worked example (example numbers)

An R-32 system with a TXV. NIST's saturation data puts R-32 at about 105°F when the gauge reads about 350 psig (roughly 365 psia at sea level)2. The nameplate target is 10°F (example).

ReadingValue
Liquid line pressure350 psig
Saturation temperature from PT data105°F
Liquid line temperature95°F
Subcooling105 − 95 = 10°F
Deviation from 10°F target0°F: pass

If the line had read 99°F, subcooling would be 6°F, which is 4°F under target and outside ENERGY STAR's ±3°F band.

Free calculatorSuperheat, subcooling & target superheat calculatorEnter pressures and line temperatures; get superheat, subcooling and a target superheat check.

Common mistakes in the math

  • Flipping the subtraction. Superheat is line minus saturation. Subcooling is saturation minus line. A negative subcooling number usually means the subtraction was reversed or the line is full of flash gas.
  • Wrong refrigerant on the gauge. R-410A and R-32 are close but not identical. Pick the one on the nameplate.
  • Probe in the sun. A liquid line clamp in direct sun reads high, which shows up as low subcooling.

What should subcooling be?

TXV and EEV systems. Use the manufacturer's target, usually on the outdoor unit's nameplate or charging chart. ENERGY STAR's commissioning checklist passes a TXV system when subcooling is within ±3°F of that target3. DOE's guide gives the same band and the same direction: remove refrigerant if subcooling is more than 3°F above target, add if it's more than 3°F below1. It also notes California Energy Commission testing that found subcooling from 2°F under to 8°F over target cost no more than 5% of normalized sensible EER1.

Fixed-orifice systems. They're charged by superheat and often have no subcooling target. DOE's guide says about 10°F, plus or minus 5°F, is typical, and recommends measuring it anyway to make sure the piston is getting solid liquid1.

Weather matters. Subcooling falls as outdoor temperature rises. DOE's guide says it may drop to zero above 105°F and that about 25°F can be expected at 70°F outdoor on fixed-orifice systems1.

What causes high or low subcooling?

ReadingSuperheatLikely cause
High subcoolingLow or normalOvercharge
High subcoolingHighRestriction: filter drier, kinked liquid line, TXV not opening
Low subcoolingHighUndercharge, often a leak
Low subcoolingLow or normalPossible bad TXV or very high outdoor temperature; check airflow and the condenser coil

DOE's guide adds a third reading, condensing temperature over ambient (COA): condenser saturation temperature minus the air entering the condenser. A COA of 30°F or more can point to an overcharge, a liquid line restriction or non-condensables, and superheat and subcooling sort out which1.

Subcooling vs superheat

 SubcoolingSuperheat
Side of the systemHigh side, liquid lineLow side, suction line
FormulaSaturation temp − line tempLine temp − saturation temp
Charge by it onTXV and EEV systemsFixed-orifice systems
Target fromNameplate or install manualChart using indoor wet bulb and outdoor dry bulb
ENERGY STAR pass band±3°F±5°F
On a blend's PT chartBubble (liquid) sideDew (vapor) side

Source: ENERGY STAR National HVAC Commissioning Checklist, Rev. 14; DOE Building America measure guideline

See superheat for the vapor side, and temperature split for the quick airside check that comes before either.

Before you add or recover refrigerant

  • Airflow is at least 300 CFM per ton (DOE's minimum for valid charge tests)
  • Filter and evaporator coil are clean
  • Condenser coil is clean and the fan is running
  • Outdoor temperature is above 55°F, ideally above 70°F
  • Both superheat and subcooling are recorded
  • The amount added or recovered is written down for the refrigerant log

How subcooling shows up in TradesWork

In the TradesWork technician app, the subcooling calculator runs offline, and the reading can be saved to the equipment record next to superheat and temperature split. When a tech adds or recovers refrigerant, the amount goes into the refrigerant log for that unit, which calculates the leak rate on save. See warranty and refrigerant tracking. The manufacturer's charging chart always comes first.

Footnotes

  1. D. Springer and B. Dakin, Measure Guideline: Air Conditioner Diagnostics, Maintenance, and Replacement, U.S. DOE Building America, DOE/GO-102013-3766, March 2013, pp. 15–31. https://www1.eere.energy.gov/buildings/publications/pdfs/building_america/measure_guide_air_cond_diagnostics.pdf ↩ ↩2 ↩3 ↩4 ↩5 ↩6

  2. NIST Chemistry WebBook, Thermophysical Properties of Fluid Systems, difluoromethane (R-32) saturation properties, retrieved Oct. 15, 2026. Gauge pressure assumes 14.7 psi atmospheric. https://webbook.nist.gov/chemistry/fluid/ ↩

  3. ENERGY STAR Single-Family New Homes, National HVAC Commissioning Checklist, Version 3.1 / 3.2 / 3.3 (Rev. 14), Section 2, revised Jan. 15, 2025. https://www.energystar.gov/sites/default/files/2025-01/National%20HVAC%20Commissioning%20Checklist_Rev%2014.pdf ↩

Free download

HVAC Maintenance Checklist (Cooling + Heating)

Printable tune-up checklists for AC, heat pump and furnace visits, with readings to record.

Get it free
  • Cooling / heat pump tune-up checklist
  • Gas furnace tune-up checklist
  • Readings log: superheat, subcooling, static pressure, temperature split, amps
  • Customer recommendations section

Frequently asked questions

On TXV systems, the manufacturer's target, usually printed on the outdoor unit or in the install manual. ENERGY STAR's checklist passes a system within ±3°F of it. Fixed-orifice systems often have no subcooling target; DOE's Building America guide says about 10°F, plus or minus 5°F, is typical for them.